MAINS POWER SUPPLY RATING | 90V AC to 230V AC |
PRIMARY DC SUPPLY | 28.5V DC @ 2.4 A (Max) |
SECONDARY SUPPLY | 21.6 (Min) – 27.2V DC (Max) – Battery charger: 27.5V DC |
BATTERY MAX. CAPACITY (INTERNAL) | Standard box: 2x 12V 7AH; Deep box: 2x 12V 12AH |
QUIESCENT CURRENT (NO DEVICES) | 52mA |
AUX POWER OUTPUT | 2 x 24V DC 300mA / 1 x 24V switched output |
MAXIMUM LOOP OUTPUT CURRENT | 1 loop – 900mA alarm peak/165mA quiescent |
LOOP TOPOLOGY | Class A (loop) or Class B (radial) |
LOOP CABLE | Fire resistant 2 x 1.5mm (max 1200m) or 2 x 2.5mm (max 2000m) |
CONVENTIONAL SOUNDER CIRCUITS | 500mA for conventional sounder circuits a+b |
AUX. RELAYS FIRE | 2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive |
AUX. RELAY FAULT | 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive |
GRAPHICAL LCD DISPLAY | High definition, high contrast blue backlit 240×64 pixels |
COMMUNICATION CHANNELS | 2 x configurable communication ports |
BMS OUTPUT | ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4 |
SOFTWARE CONNECTION | USB type B |
EVENT LOG | 10000 events |
OPERATING / STORAGE TEMPERATURE | -10ºC to 50ºC |
HUMIDITY | Max. 85% RH Non-Condensing |
INGRESS PROTECTION / MATERIAL | IP30 / ABS |
DIMENSIONS | Standard box: 273 (L) x 404 (H) x 107 (W) mm; Deep: 273 (L) x 404 (H) x 142 (W) mm |
WEIGHT | 1.6 KG (no batteries) |
ENCLOSURE COLOURS | White (RAL 9003), Red (RAL 3001) or Anthracite (RAL 7016) |
GFE – G-One
The G-One is a versatile addressable single loop fire control panel with advanced connectivity and is fully CPR certified to EN54-2 and EN54-4. Designed with affordability and flexibility in mind, the G-One combines sophisticated design with easy installation and intuitive commissioning, making it the ideal solution for a wide range of single loop applications, from offices and restaurants, to shops, schools and more. The G-One incorporates sophisticated Chameleon peer-to-peer multi-master network communications and powerful cause and effect programming capability. It can be networked with up to 32 fire control panels from the GFE range and has a high-integrity digital protocol for resilient high-speed monitoring and data communication with up to 250 devices on a single loop. Easy to install, programme and operate, the G-One can be either surface or recessed mounted. A unique installer-friendly dynamic, automatic self-learn facility bypasses the traditional manually initiated auto-learn process. Other features include a unique high resolution back-lit blue graphical LCD display, which ensures a clear and effective user interface. The G-One is fully compatible with all GFE-manufactured digital analogue-addressable loop devices and its menu structure is identical to existing GFE panels, ensuring familiarity and ease of operation for users.TECHNICAL SPECIFICATIONS
DOWNLOADS
- GFE - G-One Data Sheet+