PRIMARY SUPPLY VOLTAGE – IN |
230V AC +10% -15% |
PRIMARY SUPPLY VOLTAGE- OUT |
28.5V DC nominal |
PRIMARY SUPPLY CURRENT-OUT |
1.7A @ 28.5V DC nominal (max.) |
SECONDARY SUPPLY VOLTAGE |
21.0 min. – 27.2 max. V DC – BAT charger o/p 28V DC |
SECONDARY SUPPLY CURRENT OUTPUT |
1.85 Amp maximum @ 20 o C |
INTERNAL BATTERY CAPACITY – MAXIMUM |
2 x 12V x 7Ah Sealed VRLA Lead Acid Batteries |
MAINS FUSE |
4 A 250 V Slow Blow – 20 mm |
BATTERY FUSE |
1.85 Amp – Resettable |
NUMBER OF DETECTION ZONES |
2 / 4 / 8 |
ZONE CURRENT – QUIESCENT / ALARM |
10 mA / 60 mA maximum |
MAX. CABLE RESISTANCE / CAPACITANCE |
40 Ohms / 0.470 uF |
END OF LINE MONITORING |
Active EOL – 10uF/50V Bipolar Capacitor |
BS5839 DETECTOR REMOVAL COMPLIANT |
YES provided diodes are fitted to detector base |
DEVICES PER ZONE |
32 maximum – EN54 pt.2 |
ALARM RESISTANCE VALUE: INPUTS |
270 – 1000 Ohms |
MAXIMUM CURRENT: OUTPUTS |
1,85A maximum current drive for both S1 & S2 circuits; 100 mA for RM output |
VOLTAGE OUTPUT |
27.5V DC nominal |
END OF LINE RESISTOR: S1 & S2; RM |
S1 & S2: 10K Ohms – 1/4 Watt; RM: 4K7 Ohms – 1/4 Watt |
AUXILIARY RELAY OUTPUT |
1 Fire (COM-NC-NO) – 1 Fault (COM-NC) non-supervised |
RELAY CONTACT RATING |
30V DC – 2A / 230V AC – 0.25A (resistive loads) |
EVACUATION AND RESET |
Non-Latching – Voltage free contact |
MAXIMUM HUMIDITY |
95% RH Non-Condensing |
PROTECTION RATING |
IP30 |
OPERATING TEMPERATURE |
-10ºC to 50ºC |
WEIGHT |
1.7 Kg – 7 Kg (inc. 2 x 7 AH 12 V bat.) |
DIMENSIONS |
273 (L) x 107 (W) x 404 (H) mm |
COLOUR |
White or Red |