GFE – OCTO+

The OCTO + Fire Alarm Control Panel is built on the pedigree of the worldwide known JUNO NET. Now featuring a fully peer-to-peer, multi-master networking solution this new ‘Chameleon Network’ solution offers extreme resilience in very large distributed systems. In the Chameleon Network system, each network NODE+ retains information about the whole system in its internal memory, which means that in the unlikely event of a communication loss, the performance of each individual NODE+ is unaffected.

TECHNICAL SPECIFICATIONS

POWER SUPPLY RATING 90V AC to 230V AC
PRIMARY DC SUPPLY 28.5V DC @ 2.4 A (Max.)
SECONDARY SUPPLY 21.6V DC (Min.) – 27.2V DC (Max.) – Battery charger: 27.5V DC
BATTERIES (INTERNAL) 2x 12V 12 AH (Max.)
QUIESCENT CURRENT (NO DEVICES) 64mA
AUX POWER OUTPUT 2x 24V DC 300mA / up to 1x 24V switched out
MAXIMUM LOOP OUTPUT CURRENT 1-4 loop – Max. 165mA per loop quiescent / Max. 900mA per loop peak
LOOP TOPOLOGY Class A or B
DETECTOR CABLE Firetuf 2 x 1.5mm (Max. 1200m) or 2 x 2.5mm (Max. 2000m)
CONVENTIONAL SOUNDER CIRCUITS 500mA for conventional sounder circuits a+b
AUX. RELAYS FIRE 2x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
AUX. RELAY FAULT 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
GRAPHICAL LCD DISPLAY 240×64 pixels blue backlit
COMMUNICATION CHANNELS 3x configurable communication ports
BMS OUTPUT ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
SOFTWARE CONNECTION USB type B
EVENT LOG 10,000 messages
OPERATING / STORAGE TEMPERATURE -10ºC to 50ºC
HUMIDITY Max. 85% RH Non-Condensing
INGRESS PROTECTION / MATERIAL IP30 / ABS
DIMENSIONS 345 (L) x 375 (H) x 139 (W) mm
WEIGHT 7,5 Kg – 10,5 Kg (inc. battery)
COLOUR White (RAL 9003), Red (RAL 3001) or Anthracite (RAL 7016)