POWER SUPPLY RATING | 90V AC to 230V AC |
PRIMARY DC SUPPLY | 28.5V DC @ 2.4 A (Max.) |
SECONDARY SUPPLY | 21.6V DC (Min.) – 27.2V DC (Max.) – Battery charger: 27.5V DC |
BATTERIES (INTERNAL) | 2x 12V 12 AH (Max.) |
QUIESCENT CURRENT (NO DEVICES) | 64mA |
AUX POWER OUTPUT | 2x 24V DC 300mA / up to 1x 24V switched out |
MAXIMUM LOOP OUTPUT CURRENT | 1-4 loop – Max. 165mA per loop quiescent / Max. 900mA per loop peak |
LOOP TOPOLOGY | Class A or B |
DETECTOR CABLE | Firetuf 2 x 1.5mm (Max. 1200m) or 2 x 2.5mm (Max. 2000m) |
CONVENTIONAL SOUNDER CIRCUITS | 500mA for conventional sounder circuits a+b |
AUX. RELAYS FIRE | 2x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive |
AUX. RELAY FAULT | 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive |
GRAPHICAL LCD DISPLAY | 240×64 pixels blue backlit |
COMMUNICATION CHANNELS | 3x configurable communication ports |
BMS OUTPUT | ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4 |
SOFTWARE CONNECTION | USB type B |
EVENT LOG | 10,000 messages |
OPERATING / STORAGE TEMPERATURE | -10ºC to 50ºC |
HUMIDITY | Max. 85% RH Non-Condensing |
INGRESS PROTECTION / MATERIAL | IP30 / ABS |
DIMENSIONS | 345 (L) x 375 (H) x 139 (W) mm |
WEIGHT | 7,5 Kg – 10,5 Kg (inc. battery) |
COLOUR | White (RAL 9003), Red (RAL 3001) or Anthracite (RAL 7016) |
GFE – OCTO+
The OCTO + Fire Alarm Control Panel is built on the pedigree of the worldwide known JUNO NET. Now featuring a fully peer-to-peer, multi-master networking solution this new ‘Chameleon Network’ solution offers extreme resilience in very large distributed systems.
In the Chameleon Network system, each network NODE+ retains information about the whole system in its internal memory, which means that in the unlikely event of a communication loss, the performance of each individual NODE+ is unaffected.
TECHNICAL SPECIFICATIONS
DOWNLOADS
- GFE - OCTO+ Data Sheet+